dc.identifier.citationBenasla , M , Denai , M , Liang , J , Allaoui , T & Brahami , M 2021 , ' Performance of wide-area power system stabilizers during major system upsets: investigation and proposal of solutions ' , Electrical Engineering . https://doi.org/10.1007/s00202-020-01168-3
dc.identifier.issn0948-7921
dc.identifier.urihttp://hdl.handle.net/2299/23798
dc.description© 2021 Springer Nature Switzerland AG. This is a post-peer-review, pre-copyedit version of Benasla, M., Denaï, M., Liang, J. et al. Performance of wide-area power system stabilizers during major system upsets: investigation and proposal of solutions. Electr Eng (2021). The final authenticated version is available online https://doi.org/10.1007/s00202-020-01168-3
dc.description.abstractWide-area damping controllers (WADCs) are effective means of improving the damping of inter-area oscillations and thereby ensuring a secure operation of modern highly stressed interconnected power systems; however, their implementation costs are high. Therefore, the controller must be well configured and designed to ensure its cost-effectiveness. Several techniques have been proposed in the literature to design effective controllers and good results have been achieved. However, some important practical aspects that could potentially impact the performance of the designed controller have not been addressed or studied in sufficient detail in these previous works. One such aspect is assessing the performance of the designed controllers under major system upsets resulting in large deviations in the frequency and fluctuations in the power. These may lead to controller saturation which could negatively impact its damping performance or even cause instability. In this paper, the impact of such large upsets is investigated on several test systems via extensive small- and large-signal analyses and it is shown that, during severe transients, controller saturation may occur and persist over a long period of time, posing a potential threat to the power system stability. This paper presents a very effective solution to alleviate this problem and help design more robust WADCs. The simulation results show that the proposed solution works well and leads to improved power system stabilisers performance during transient upsets.en
dc.format.extent2407205
dc.language.isoeng
dc.relation.ispartofElectrical Engineering
dc.subjectInter-area oscillations
dc.subjectPower system stabilizer
dc.subjectSaturation limits
dc.subjectTransient stability
dc.subjectWide-area damping controller
dc.subjectElectrical and Electronic Engineering
dc.subjectApplied Mathematics
dc.titlePerformance of wide-area power system stabilizers during major system upsets: investigation and proposal of solutionsen
dc.contributor.institutionCentre for Engineering Research
dc.contributor.institutionCommunications and Intelligent Systems
dc.contributor.institutionSchool of Physics, Engineering & Computer Science
dc.contributor.institutionDepartment of Engineering and Technology
dc.description.statusPeer reviewed
dc.date.embargoedUntil2022-01-03
dc.identifier.urlhttp://www.scopus.com/inward/record.url?scp=85098656065&partnerID=8YFLogxK
dc.identifier.urlhttps://rdcu.be/cc1aZ
rioxxterms.versionofrecord10.1007/s00202-020-01168-3
rioxxterms.typeJournal Article/Review
herts.preservation.rarelyaccessedtrue


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record